free tracking

Air Temperature Control Unit SS-2400

The ATCU SS-2400 accommodates enclosure:
Area: Up to 6 m²
Volume: Up to 4 m³

Using solid state technology, the ATCU SS-2400 model accommodates enclosures up to 6 m² and will maintain the temperature at the Critical Point to 0.001 p-v (± 0.002) °C.

ACTU SS-2400 Specifications

Performance Stability when Ambient ±1°C

Stability at Critical Point: 0.01 p-v (± 0.005) °C.
Set-point: Ambient ± 1 °C.
Operating Conditions: 18 - 24 °C.
Air Flow Rates (m³/min): 10 - 25, adjustable.

Performance Stability when Ambient ±.1°C

Stability at Critical Point: 0.001 p-v (± 0.0005) °C.
Set-point: Ambient ± .1 °C.
Operating Conditions: 18 - 24 °C.
Air Flow Rates (m³/min): 10 - 25, adjustable.
Sound Level: 60 dBA.
Cooling Capacity: 2400 W

Electrical 

Voltage (V): 208/230 ± 10%.
Phase: 1.
Frequency (Hz): 50/60.
Max. Nominal Current - Cooling (A): 13.
Max. Nominal Power Consumption (kW): 2.8.
Breaker/Fuse Size (A): 10.
Supply Power Wire Size (AWG): 1.

Sound Level: 60 dBA.
Cooling Capacity: 1200 W.

Heat Loads from Praecis Equipment

Exhaust heat capacity: 8,189 BTU/hr
Total unit exhaust heat: 16,378 BTU/hr

ENCLOSURE SIZE

Enclosure area:  Up to 6 m².
Enclosure volume:  Up to 4 m³.

PHYSICAL CHARACTERISTICS

Height: 1.88 m.
Width: 0.91 m.
Depth: 1.37 m.

Weight (kg): 170 kg.
HEPA Filtration: Optional

USER INTERFACE

Control:  Laptop PC.
Data storage:  Thermograph/PC.
Data recording format:  Excel, text. 
Channels:  Up to 8 channels of data.
Software:  Robust and user-friendly.
High/Low temperature alarm:  Yes.
Selectable sampling intervals:  Yes.
Moving average filtering:  Yes.
Adjustments:  Programmable set points.
Remote tuning from Præcis:  Yes.
User manuals:  English.

Floor loading and rigging

Unit weight: 170 kg, 42.64 kg per caster
Dimensions: 1.8 x 1.37 x 0.91 m

doorway openings Accomodation:

Standard doorway: 2.03 in x 0.91 m
Turn clearance:
1.12 m